In Brief Description:

12 VDC, Probe is PT100, Temp range -50 to 400 C. Output PID variable voltage 0 to 12 VDC or just on/off (0VDC/12VDC)

NO panel   Description

1 PV   measured data

2 SV  target data

3 RUN mode light

4 Hi high temp. alarm

5 Lo Low temp. alarm

6 SET to set data

7 < move/run/stop

8 - decrease

9 + increase

SET Temp:

When normal display, press "SET", it will appear SC1 -> TC1 -> AL1 -> AH1 ->SC2 ->TC2 ->AL2 ->AH2 ->SC3 ->TC3 ->AL3 ->AH3 ->SC3 ->TC3 ->AL3 ->AH3 ->SC4 ->TC4 ->AL4 ->AH4,  under each parameter, by press "<, +,_" to enter  corresponded  data.  If enter SC=0,  that stage and all later stages will be ignored. Press "SET" till normal display

SET Parameters

When normal display, press"SET" for 3 seconds, then press "SET" will appear F-C -> SL1 -> SL2 -> HdC. Enter data under each parameter. Press "SET" 3 seconds again back to normal display.

 When normal display, press"SET" for 9 seconds,  it will appear  P -> I -> d -> Ar -> T -> Pb ->UdC -> LCK. Enter data under each parameter. Press "SET" a few seconds till back to normal display.

SET meaning

P default 30

I second, default 240

D default 60

Ar do not change

T not in used.

Pb   probe calibration

UDC minimum fan speed

LCK do not change

F-C 0=C 1=F

SL1 not change

SL2 not change

HdC maximum fan speed, default 100%

SC1 Stage I,  Temp.

TC1 Stage I, Time minute

AL1 Low Temp. alarm

AH1 High Temp Alarm

......

SC4   Stage IV,  Temp.

TC4 Stage I,V Time minute

AL4 Low Temp. alarm

AH4 High Temp Alarm

Note

*1 When P=0 On/Off mode, activating temperature 3 C.

When P0   PID Outputneed to fine tune P,I,D to fit your very own pit

*2 Minimum fan speedUDC

    Press "SET" till appear "UD", then press "<", then press "+" or "-" till the fan begin to running. Press"SET" again" to normal display

*3 LCK,  do not change, but meaning is

A.. LCK=0000all parameters can be chaned

B .LCK=0001 ,SVAL1AL2 can be changed, all other parameters can not be changed

C.. LCK=0011SV can be changed, all other parameters can not be changed

D. LCK=0111all parameters can not be changed

*4 Maximum fan speed HdC

  Indeed Hdc is  percent of maximum voltage, in turn maximum an speed

When DOG is in auto mode, press"<" to end it and change to "manual mode", if press "<" again change to "AUTO" mode again and starts over a new  course.

When

When Manual mode, if RUN blinks, press "+" or "-" to change output voltage and in turn fan speed

Restore to Default

1.turn off power swith for 3 seconds

2.Press "<" and hold,

3.turn power swith on, it will show "8888", then "1111","2222","3333", then release "<"

Error shooting

When PV display‘————‘bad probe

When Hi/Lo in red and blinks, high or low temp alarm

When PV blinks, measured temp. Is beyond the  maximum range

When SV--:-- and blinks,program ends normally

When manual model, SVshows----

When PV inErr, please do operation of "restore default"